Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
59 Cards in this Set
- Front
- Back
A burner must be started in a particular sequence to ensure ____ |
Safe startup |
|
A ____ cycle is a predetermined period of time during which air is blown through the furnace to remove any combustible vapors |
Purge |
|
A ____ is used to sense the pilot and main flame in the burner |
Flame sensor |
|
Proving the main flame is sighting the main flame through a flame scanner to verify that the ____ |
Main flame is lit |
|
____ is a purge that occurs after burner shutdown |
Postpurge |
|
If steam is being used faster than it is being generated, the steam pressure _____ |
Decreases |
|
_____ can be used in plants where the steam load is steady and allows the burner to be started and stopped |
ON/OFF control |
|
A(n) _____ is a combination control system that is used to adjust the firing rate to a degree that is proportional to the steam load |
Modulating control system |
|
A(n) _____ is a combustion control system in which the flow of fuel and air are measured and adjusted in correct proportions based on steam pressure |
Metering control system |
|
Combustion controls use signals sent from measuring instruments to the controller and from the controller to a(n) ____ that changes flow |
Final element |
|
The primary function of a combustion control system is to regulate the _____ in a boiler |
Fuel supply, air supply, draft |
|
ON/OFF control is used to start and stop a burner without doing what? _____ |
Without modulating the flame to match steam load |
|
A siphon is used to protect an operating pressure control from ____ |
Live steam |
|
An operating pressure control must be connected to the _____ |
Highest part of the steam side of the boiler |
|
The two settings found on the boiler operating pressure control are used to _____ |
Set the operating steam pressure range of the boiler |
|
The combustion blower continues to run after fuel is shut off to the burner during ____ |
Postpurging |
|
To eliminate the danger of a furnace explosion during startup, the programmer must allow _____ |
A prepurge period |
|
The purpose of the flame sensor in a flame scanner is to prove _____ |
Both the pilot and the main flame |
|
A flame sensor is sensitive to ____ |
Infrared, visible, or ultraviolet light |
|
In the event of a flame failure, the programmer _____ |
Shuts the burner down |
|
A modulating control system is sensitive to changes in the ____ |
Steam pressure |
|
A(n) _____ is a controller that distributes steam production requirements across several boilers to maintain the steam pressure at the setpoint |
Plant master |
|
A preignition check includes _____ |
Verifying that the fuel pressure proving switch is closed |
|
After a programmer proves the main flame what happens to it _____ |
Releases to automatic control |
|
If steam is being used faster than it is being generated, the _____ |
Steam pressure decreases |
|
What does a high-limit pressure control have? ____ |
a manual reset |
|
The flow of fuel through valves and air through dampers is usually linear or nonlinear?_____ |
Nonlinear |
|
Single-point positioning uses the ____ as the controller input and has only one output |
Steam pressure |
|
A low firing rate needs _____ than at a high firing rate |
More excess air |
|
Parallel positioning uses steam pressure as the controller input and uses how many output signals and what are they? _____ |
Uses two output signals 1: fuel valve fuel flow 2: air damper air flow |
|
A modulating control system adjusts the firing rate proportional to the _____ |
Steam load |
|
Nonlinear flow means that the percent a valve or damper is open does not necessarily correspond to _____ |
Percent of flow |
|
The final preignition step is to ___. |
Pre-purge the furnace. |
|
A(n) ___ detects the presence of a flame and signals to the burner management system whether it is safe to operate the boiler. |
Flame scanner. |
|
A(n) ___ failure is a situation where a pilot or main flame fails to light properly or goes out unintentionally during normal operation. |
Flame. |
|
A(n) ___ is a sensing device in a flame scanner that generates a small electric current when one end of the sensor is placed directly in a flame. |
Flame rod. |
|
If there is a flame failure while a burner is firing, the signal stops and the burner management system shuts down the burner and ___. |
Purges the furnace. |
|
A burner should normally fire for ___. |
Longer periods than it is idle. |
|
The fuel flow rate is controlled by a ___. |
Valve. |
|
A(n) ___ pressure control is an ON/OFF control with a manual reset that sends a signal to the combustion control system to shut down the burner in the event of a high pressure condition that exceeds the operating pressure control cut-out setting. |
High-limit. |
|
___ positioning is a modulating control strategy that uses steam pressure as the input signal and outputs a signal to a modulating motor that turns a jackshaft to modulate the air and fuel flow. |
Single-point. |
|
The most common instrument used to measure the flow of steam is a(n) ___. |
Orifice installed in the steam line. |
|
___ is a control strategy in which increases in airflow lead increases in fuel flow, and decreases in airflow lag behind decreases in fuel flow. |
Cross-limited control. |
|
Typical blower motors operate at a constant speed at ___ Hz. |
60. |
|
Digital signals consist of ___ signals in the form of low-voltage DC pulses sent over a network, or fieldbus. |
Binary (ON/OFF). |
|
What are safety interlocks that affect the burner firing sequence? |
Preignition checks, purge cycles, lighting the pilot, lighting the main flame, and postpurge during shutdown. |
|
What are some preignition checks? |
Burner management system, operating and high-limit controls, fuel pressure proving switch, air dampers, gas pressure proving switch. |
|
Why is there an interlock during preignition? |
To prove airflow during the firing cycle. |
|
What determines how long a purge cycle will last? |
The furnace size, standard procedures, and insurance company requirements. |
|
What happens if the burner management system cannot prove that the pilot has been lit? |
The burner management system shuts down the system, purges the furnace, and initiates a flame failure alarm. |
|
Why is the flame scanner tested? |
To prevent the possibility of furnace explosion. |
|
What are the most common flame sensor types? |
photocell flame sensors, infrared flame sensors, ultraviolet flame sensors, flame rod sensors. |
|
In regards to the burner management system, what is "releasing to automatic control?" |
- After the burner management system proves the main flame it goes into "automatic control." The system continues to monitor the signal from the flame scanner. If there is a flame failure while the burner is firing, the signal stops. The burner gets shut down by the system and the furnace gets purged. |
|
How should the fire be when it's turned on and off? |
You always want to start the boiler at a low fire (flame) and shut it down with a low fire (flame). |
|
Why is steam pressure measured? |
The most common measurement used to determine the balance between steam generation and steam use. |
|
How is the control system related to steam pressure? |
The control system maintains the proper ratio of fuel and air in the burner. |
|
What is operating pressure cut-in and cut-out pressure? |
Start at a certain pressure and stop at a certain pressure. |
|
What should a boiler operator always assume when a boiler shutdown occurs? |
Assume that a safety device has functioned correctly. It is always best to assume that an unsafe condition exists than to assume a safety device is faulty. |
|
What is a purge cycle based on? |
Size of the furnace volume. |