a gauge that measures preassure above atmospheric and vacum below atmospheric preassure
|
compoung gauge
|
|
amonia absrption system
1-removes water from refrigerant |
analizer
|
|
amonia absorption
2-holds strong liquor |
generator
|
|
amonia system
3-regulates liquor flow |
weak liquor valve
|
|
amonia system
4-removes moisture from the vapor |
rectifier
|
|
amonia system
5-removes vapor from evaporator |
absorber
|
|
amonia system
type of metering device used |
manual
|
|
in a booster system the second compressor is called
|
the primary compressor
bacause it is always started first |
|
in a booster system the first compressor is called
|
the booster compressor
|
|
this stores any extra refrigerant that might be in the system and keeps it available so that the expansion valve has it when needed
|
receiver
|
|
two types of cooling towers
|
1- forced-pushes air in the tower
2-enduced-pulles air in the tower |
|
two tipes of Brines
|
1-sodium choride freezing point -6.0 fh
2-calsium chloride freezing point -59.8 fh |
|
nesslers solution
|
test water for amonia-turns
1-yellow for small leak 2-brown for large leak |
|
a preasure reducing valve that controls the flow of refrigetrant to the evaporator
|
metering device
|
|
the most efective rust inhibitors
|
chromates
1-sodium bichromate 2sodium dichromate |
|
(metering device) that is a small tank conected to the evaporator with a needle valve that regulated flow
|
low side float
|
|
1-maintains the preasure diferential between the condenser and the eveporator.
2-it feeds the proper amount or refrigerant to the evaporator. 3-it responds to the load change in the system |
thermostatic expansion valve
|
|
installed between the compressor and the condenser,as far from the compresson as possible stops oil from entering the condenser
|
oil separator
|
|
device that is temperature operates the opening or closing of the metering device.inside the valve
|
internal equalizer (TEV)
|
|
removes moisture from system
|
Driers or Dehydrators
installed usually liquid line drier |
|
remove air and other non-condesables from the system
|
purgers
|
|
when a preassure drop of more than 2 pounds in the evaporator you need a________in the metering device
|
external equalizer
|
|
a vessel or tank located in the suction line between evaporator and compressos to prevent cary over or slugging of liquid into the compressor
|
suction line accumulator
|
|
remove sludge,dirt,scale
installed before the compressor |
filters & strainers
|
|
to check the operation and efficiency of the compressor
|
engine indicator
|
|
is designed to vaporize all of the low preasure liquid that passes through the evaporator
|
dry evaporator
|
|
the temp of the refrigerant must be _________the temp of the medium being cooled
|
below
|
|
chilled water is cooled by the refrigerant than circuleted to the apt the refrigerant never enters the apt this system is called?
|
indirect system
|
|
submerged below the refrigerant are tubes that carry chilled water to cool the refrigerant
|
flooded evaporator
(horizontal shell & tube) |
|
(metering device)located in the receiver
|
higt side float
|
|
heat will always travel from the warm mass
|
to the cool mass
|
|
heat is rejected from the refrigeraton cycle by air or water at the____________
|
condenser
|
|
metering device for systems with coonstant load
water coolres,domestic ref (constant preassure valve) |
automatic expantion valve
|
|
remove noise & vibration
|
Mufflers
|
|
maitain the proper oil level in multiple compressor systems
|
oil equilizer lines
|
|
melts at 275 FH
|
fusible plug
|
|
made out of carbon or grafhite and designed to rupture at 15 PSI
|
rupture disk
|
|
during periods of low load the preassure drops,cutting of the compressor,it re-starts system when preasure rises
|
low preasure control
|
|
safety device it cuts off the system if the high side preassure exeeds a certain setting.it is not capable of re-starting the system
|
high preasure control
|
|
in an amonia absorbtion systen the______________acts like the compressor
|
the absorber
|
|
absorbtion system
the generator contains a continous sourse of__________ |
heat
|
|
trouble evaporator
A-low evaporator preassure |
1-dirty coil
2-dirty evaporator filter 3-supply air short cycling 4-oil logged 5-low refrigerant charge 6-paraffin based refrigerant oil |
|
trouble evaporator
B-high evaporator pressure |
1-system operating at maximum load
(max load preassure) expansion valve wide open |
|
trouble evaporator
low superheat |
1-manual expancion valve needs re-adjusting
2-partially blocked expansion valve 3-dirty evaporator 4-too much refrigerant being sent to the evaporator 5-TEV sensing bulb disconected from coil |
|
trouble compressor
high suction preassure,low discharge preassure(reciprocating compressor) |
compressor valves not seating properly
|
|
trouble compressor
banging sound on start up(reciprocating compressor) |
oil over charge
|
|
trouble compressor
oil foaming in crankcase(reciprocating compressor) |
1-crankcase heater not working
2-sudden drop in crankcase preassure |
|
trouble compressor
compressor surging (centrifugal) |
1-high head preasure
|
|
problem condenser
low head preasure |
1-condense water temp too low
2-under charge of refrigerant |
|
problem condenser
high head preassure |
1-over charge of refrigerant
2-not enough condenser water 3-condenser water temp to high |
|
problem liquid line
frost on liquid line |
partial blockege of liquid line
|
|
problem liquid line
bubbles in liquid line sigth glass |
loss liquid seal
shortage of refrigerant |
|
problem liquid line
liquid line warmer than usual |
loss of liquid seal
shortage of refrigerant |
|
problem liquid line
presence of water in the system |
1-blocked flow at metering device
2-sigth glass moisture indicator turns color (green to yellow) |
|
problen expansion valve
TEV starved evaporator |
1-external equilizer line blockage
2-broken sencing bulb 3-internally equilized TEV used on a coil with a preasure drop of more that 2.5 psi |
|
problem expansion valve
TEV flooded evaporator |
sensing bulb disconnected from from coil
|
|
problem expansion valve
AXV- starved evaporator at high load,flooded evaporator at low load |
automatic control valve used in a variable load system
|
|
problem expansion valve
low side float-suction preasure rising |
broken / punctured float assembly
|
|
problem expantion valve
high side float starved evaporator |
broken / puntured float assembly
|
|
problems mechanical
noisy operation |
worn bearings
|
|
problems mechanical
premature bearing wear/high running amps |
1-belt tension too high
2-pulley out of alignment 3-coupling out of alignment |
|
motor problems electrical
open windings |
ohmmeter reads (infinity)
|
|
motor problems electrical
shorted motor windings |
1-winding resistance less than the motors published value
2-less resistance causestemperature to rise,motor overload device opens circut(shut down) |
|
motor problems electrical
short circuit to grownd |
high resistance reading
use ohmmeter or megaohmmeter |
|
motor problem electrical
icorrect rotation |
reverse any two of the motor power leads
|
|
motor problem electrical
high operating temp |
high corrent
|
|
cetrifugal water pump problems
pump not delivering rated GPM |
1-discharge/suction valves partialy closed
2-pump air bound 3-pump cavitating 4-plugged strainer 5-piping coniguration altered 6-check valve in a parallel pump not seating properly |