All residential sprinklers within a compartment must have a temperature rating within what degree of one another?

10 degrees

Attic sprinklers can used in what?

With attics pitches from 4:12 to 12:12

What is used on a butterfly valve to prevent the valve from being opened or closed to quickly?

A gear operator.

What type of valve has a round disc that fits tightly in its mating seat and rotates 90° and one direction to open and allow fluid to pass through the valve?

Butterfly valve

What kind of valve provides less resistance to flow than globe valves?

Ball valve

What two sizes of hose valves are most common?

1 1/2" and 2 1/2"

What is the maximum inlet pressure allowed for pressure reducing valves that reduces pressure under flow conditions only?

175 PSI

The pressure gauge located above the clapper of the alarm valve indicates____?

System pressure

When water pressure varies a great deal, and a retard chamber is not significant to prevent false alarms, what other device can be used?

An excess pressure pump

An auxiliary drain should consist of a nipple and cap or brass plug not less than 1/2" in size when the capacity of trapped section of pipe is what?

5 gallons or less

What is the recommended amount of pipe that should be exposed in the warm area to prevent freeze damage where a test pipe extends through a wall?

Not less than 4 ft.

The term hydraulically tested means

A system has been tested with water

Unobstructed construction includes

Bar joist

What is the maximum distance between standard sprinkler in light hazard?

15 feet

What is the minimum distance for a sprinkler can be from a wall?

4"

In unobstructed construction, the deflector distance below the ceiling is what?

1 to 12 inches

A sidewall sprinkler installed under a slope ceiling must be located where?

Located at the high point of the ceiling and positioned to discharge downward

The sum of 1 3/4, 6 3/8, 1 23/32

9 27/32

What is the square footage of 8 ft 6 in x 10 ft 9 in

91. 375 square feet

For every foot of vertical rise the head pressure conversion factor is what?

. 433

The minimum allowable operating pressure applied to a standard sprinkler is

7 PSI

The reflected ceiling plan view of a blueprint will not show?

Rough contours

Information on any changes that have been made to the drawing will be located in the what?

Revision block

What is the maximum allowable sprinkler spacing for a hydraulically calculated system in a building, used for high piled storage, with combustible obstructed ceiling construction?

100 sq. ft

The maximum unsupported length on the end of a branch line with 1" schedule 40 steel pipe?

36"

What is the maximum distance between hangers on 1" and 1 1/4" schedule 40 steel pipe?

12 feet

In fire protection work, the decision point for dry sprinkler system versus what is set at what temperature?

40° F

What is the maximum allowable working pressure for a sprinkler system?

175 PSI

A pressure measured on the water supply under no fire flow condition is called what?

Static pressure

Properly installed surface tanks require what?

Concrete foundation, pressure relief provision, pump and lighting protection.

A pit must be large enough to hold all the equipment to be installed into it in addition it should be what

Have an access port adequate to allow servicing and replacing of the device within it.

The basic NFPA standard for classification of standpipes is what

NFPA 14

If a 45° offset is 5 ft the rise or run is

3' 6 1/2"