What backflow prevention devices protect against, other than back siphonage low and high hazard.

Double check valve, backflow preventer for carbonated beverage dispensers, double check fire, and rps.

What do most backflow prevention devices protect against

Backsiphonage low Hazard and high hazards

What does a backflow preventer for carbonated beverage dispenser protect against

Backsiphonage low hazard

What is a double check valve backflow preventer good for

Back siphonage and back pressure but only low hazard

What two materials can only be used for building supply pipe and fittings.

PVC and polyethylene

What are the three pressure ranges for determining water pipe and meter sizes

30 to 45 46 to 6 and over 60


P fixture unit values for water closet flushometer valve

40 30 20 15 10

Fixture unit values for urinal flushometer valves

20 15 10 8 5

Sizing of residential water softeners

Three-quarter inch connection up to two bathroom group served.


1 inch connection up to for bathroom group served.

Maximum trap arm length for a floor drain to hit a vented line 2 inch through 6 in.

610 14 20

Maximum horizontal trap arm length except for water closets and similar fixtures

2'6" 3'6" 5' 6' 10'

Minimum horizontal distance from a building or structure

5 foot

Minimum horizontal distance required from building sewer to a property line adjoining private property

Clear

Minimum horizontal distance required from building sewer 2 water supply Wells

Not less than 50 feet or 25 foot if constructed of materials approved for inside the building.

Minimum horizontal distance required from building sewer to streams

50 feet

Minimum horizontal distance required from building sewer to on-site water service line

1 foot but must be 12 in above on a permanent shelf and 12 in over.

Minimum horizontal distance required from building sewer to a public water main

10 feet for parallel for crossing it needs to be approved by Oregon Health Authority or building official

Threads per inch on clean-out up to 2 in?

11 + 1/2

Number of threads per inch on cleanouts 2 and 1/2 inch and larger

8 per inch

Maximum unit loading and maximum length of drainage and vent piping.

1 2 16 48 256


1 2 8 35 216


45 65 85 212 300


1 8 24 84 256


45 60 120 212 300

Maximum drainage fixture units for trap and trap arm 1 1/4"through 4"

1 3 4 6 8

Discharge capacity in gallons per minute for intermittent flow


Up to 7 1/2


7 1/2-15


15-30


30-50

1 2 4 6

P public drainage fixture units for food waste disposal commercial

3 fixture units

Waste fixture units for a floor drain that is not emergency

2

Drainage fixture units for wash fountains

2 + 3

Drinking fountain waste fixture units for public-private and assembly

.5 .5 and 1

What three waste materials can only be used above ground drain waste and vent pipe and

Galvi steel galvi malleable iron and stainless 304

What two materials for Waste drain and vent pipe can only be used on building sewer and pipe and fittings

Polyethylene and vitrified clay.

What type of copper can you not use underground inside a structure but everywhere else

Type M copper

Colors for type k type l and type m copper

K green L blue M red

Corrugated fixture connectors for fixture connectors, washing machine connectors, dishwasher and ice maker connectors

Fix your connectors 30in, washing machine connectors, 72in dishwasher and ice maker connectors 120in

Max distance on corrugated flexible water heater connectors

24in

Minimum and maximum on clothes washer standpipe receptors

P-trap no lower than 6 in no higher than 18 in. Tailpiece no less than 18 in no more than 30 in 6-18 and 18_30

Pipe and tube size for rod size 3/8 of an inch 1/2f an inch and 5/8 of an inch

3/8 (1/2-4)


1/2 (5-8)


5/8 (10-12)

Minimums for hydro-mechanical grease interceptor

8 dfu


20 gpm

Water distribution minimum are gaps where affected by side walls for 1/2" 3/4" and 1"

1/2" - 1 1/2


3/4"- 2 1/4


1"- 3


Above 1" 3x

Caulking ferrules table- length of all caulking ferals 2 through 4 in

4 1/2"

Bathtub or combo bathtub shower water fixture units private

4

Three-quarter inch bathtub filled valve private water fixture units

10

Private water fixture units bidet

1

Private water fixture units clothes washer

4

Private water fixture units drinking fountain

.5

Private water fixture units hose bib

2.5

Private fixture units water supply Mobile home

12

Water fixture units private bar sink

1

How many fixture units are on all sinks for private except for bar sink which is one fixture unit

1.5

Water fixture units private shower per head

2

Water fixture units urinal flush tank private

2

Water fixture units private water closet greater than 1.6

3

1.6 WC private water fixture units

2.5

Gravity grease interceptor minimum sizing fixture units and volume

8 and 500

These two materials need vertical support how cast iron. cast iron no hub.

Base and each floor not to exceed 15 ft.

Copper and copper alloy support horizontal and vertical

Horizontal-inch and a half and smaller every 6 feet. 2 inch and larger every 10 ft


Vertical-each floor and not to exceed 10 feet


Horizontal and vertical support for steel pipe -water or dwv

Horizontal 3/4 " and smaller 10 feet


1 inch and larger every 12 ft


Vertically every other floor not to exceed 25 ft

Supports for steel pipe for gas

Horizontally 1/2 inch every 6 ft 3/4 of an inch and 1 in every 8 feet inch and a quarter and larger every 10 ft


Vertically half inch every 6 ft 3/4 of an inch to one in every 8 ft inch and a quarter every other floor level

Supports for schedule 40 PVC and abs dwv

Horizontally every 4 ft and allow for expansion every 30 feet


Vertically bass and each floor provide mid-story guides provide for expansion every 30 ft

CPVC supports

Horizontally 1 inch and smaller every 3 feet


Inch and a quarter and larger every 4 ft


Vertically bass and each floor provide mid-story guides

Support for lead pipe

Horizontally continuous support


Vertical not-to-exceed for feet

Support for steel pipe with mechanical joints

In accordance with standards acceptable to the building official

Support for pex piping

Horizontally 1 inch and smaller every 32 in, inch and a quarter and larger every 4 ft.


Vertically base at each floor provide mid-story guides.

Support for PEX Al PEX

Horizontally every 98 in


Vertically bass and each floor provide mid-story guides

Pe Al pe supports

Horizontally every 98 in


Vertically bass and each floor provide mid-story guides

Pe-rt supports

Horizontally one in smaller every 32 in


Inch and a quarter and larger every four feet


Vertically bass and each floor provide mid story guide.... I left a hint for this one

It's the same as PEX

every indirect waste receptor receiving discharge containing particles that would clog the receptor drain shall have a removable blank strainer

Beehive

A steam blow off condenser with an outlet of inch-and-a-half requires event size of

4 inch minimum


Vent pipes for outdoor insulation she'll extend at least blank feet above ground

10 ft


Where must a clean out be for an interceptor

Outside such interceptor

Clothes washers in batteries of blank or more shall be rated at blank fixture units each

Batteries of three or more shall be rated at 6 fixture units each

When are backwater valves required in the drainage piping system

When fixtures are installed on a floor level is lower than the next upstream manhole

When can you install combination waste and vent systems

Only when you have structural conditions


What is the minimum vent pipe sizing in Frost areas below zero degrees Fahrenheit

2 inch diameter pipe

Can you intersect chemical waste venting with other services

No

When can you skip a clean-out on a building sewer

When it's a straight run and under 10 ft

What are the criteria for running a building sewer less than 1/4 of an inch grade

4 inch and over and with prior approval from the building official

caulk joints for cast-iron Bell and spigot pipe and other similar joints shall be firmly packed with oakum and filled with molten lead to a depth of not less than

1 in

How many fixture units are a water closet on waist worth if hooked to a septic system

6 fixture units a piece Biotch!!;

What length must a vertical wet vent not exceed

6 feet

What are the max fixture units that a vertically wet method fixture can have per fixture

1 and 2 fixture units

What distance off the floor must a yoke vent connect

42 in

How many pipe sizes larger must have vertical barrel of a fitting be to receive waist on a vertically wet vented system

1 pipe size larger

On a horizontally wet method system how many fixture units can you run on 2 inch and 3 inch portions

463 units maximum on 2in. And side in or more on 3 in

Maximum indirect waste pipe length for a refrigeration coil drain

Unlimited

Minimum size indirect waste line for ice making machine

1/2 of an inch

Minimum thickness of lead pipe that can carry chemical waste

Quarter of an inch thickness

minimum vent required for a sump or receiving tank shall be blank inches. The minimum vent for a sump receiving tank which has a water closet draining into it is blank

Inch and a half without. 2in with a water closet on it

Do you need audio and visual alarms for ejector system on single dwelling units

No

How high must you flagpole a vent terminating in a roof area used for sunbathing

7 feet

10 buildings over 10 stories how often must you run a relief vent and yoke vent

Every five stories

We're copper flashing is used for roof drains it should be of what weight minimum

12 oz minimum

What chapter talks about non-potable applications

Chapter 15

Maximum velocity for hot water in copper tube

5

Water heater attic access minimum

22 x 30

a pressure release valve used in lieu of an expansion tank shall have a maximum setting of blank PSI when designed by a registered design professional

100

T&p drain terminating on a non grade garage floor shall be no less than blank and no more than blank from the floor

No less than 6 in and no more than 12 in off the floor

Restaurant kitchen sinks must be of what gauge ponderize and galvanized

16 gauge

What size shower is exempt from the 30-inch circle rule

I shower with 30 by 60 dimensions

Where are floor drains required

restrooms with two or more water closets or a combo of water closet and a urinal except in a dwelling unit. Commercial kitchen, commercial laundry, and boiler rooms

Two installations were provisions in this code for acid waste requirements do not apply

X-ray dark rooms and control laboratories

Sand pipes for outdoor installations shall extend at least blank feet above the ground

10 ft

Where does the clean-out for an interceptor go

Outside of such interceptor

For reaching the two times barrel size for a double sanitary tee what sizes are

2 2 and 1/2 3 3 and 1/2 for 4 and 1/2 5/6

Minimum distance from Center to sidewall obstruction for a bday or water closet

15 in

Minimum clear space in front of a water closet lav or the day shall be not less than

24 in

In dwellings in dwelling units minimum space in front of a water closet for bidet

21"

Flow rate for shower heads commercial and residential

2.5 gallons per minute commercial 2 gallons per minute residential

Outlet and fixture tailpiece for a shower minimum

2 in

Max water consumption in urinals

1 gallon per flush

Water consumption in water closets residential and commercial

Residential 1.28 / flush commercial 1.6 / flush

Drainage fixture units bathtub private

2 fixture units

Drainage fixture units private the day inch and a quarter trap arm

1 fixture unit

Drainage fixture units clothes washer domestic standpipe

3 fixture units

Drainage fixture units dental unit cuspidor public

1 fu

Drainage fixture unit dishwasher domestic with independent drain

2 fixture units

Drain fixture units drinking fountain or water cooler

.5 fixture units

Drain fixture units food waste disposal commercial

3 fu

Drain fixture units floor drain emergency

0 fu

Drain fixture units floor drain non-emergency

2 fu

Drainage fixture units showerhead single trap

Two fu

Drainage fixture units multi-head each additional

1 fu

Lavatory drain fu

1fu

Drainage fixture units lavatory in sets

2 fu

Drain SU bar sink

1 fu

The first two special-purpose sinks drain fixture units

2 and 3

Drainage fixture units kitchen domestic with or without food waste disposer dishwasher or both

2.0

Drainage fixture units laundry tray or laundry sink

2 fu

Drainage fixture units mop sink or mop basin

3 fu

Drainage fixture units urinals

2 fu

Water closet fixture units under 1.6 gallons per flush private

3 fu

Water closet drainage fixture units 1.6 gallons per flush public

4 fu

Water closet 1.6 gallons per flush drainage fixture units assembly

6 fu

Drainage fixture units water closet over 1.6 gallons per flush private

4 fu

Drainage fixture units water closet 1.6 gallons per flush drainage assembly

6 fu

Water closets greater than 1.6 gallons per flush assembly drainage

8 fu