26.) other than class two conductors lighting systems operating at 24 V will have their transformer secondary current limited to a largest of?

3. 25 amps


411.3

A transformer has a 75 kVA rating and is 460 V three phase with an efficiency of 90° what’s the impasse is it in ampacity necessary for the primary wire?

104.6 amps


(75*1000)/ (1.732*460*90)

28.) A jewelry store has two 15 foot show windows one on either side of the entranceway what’s the smallest number of receptacles necessary to service these windows?

2 per window


220.43 / 220.14(G)

29.) When using threaded fittings in a class one division one area a minimum of how many threads must be engaged?

5 threads


500.8 (E)(1)

30.) A three phase motor controller is also the disconnect it is required to open

All 3 phases

31.) 480/ 277 V feeder utilized at 400 A is run from building one of the building 2 the branch circuits originate in the second building and serve mostly motor loads in the building what’s the smaller size grounding wire allowed to run in the second building

3 awg


Table 250.122

32.) A non-metallic sheathed cable of 60° rated wires feeds a panel that needs grounding it is utilized at 60 A what size copper equipment grounding wire is required?


#10


Table 250.122

33.) what’s the Ampacity of three 1 gauge THW copper wires in a race way at an ambient temperature of 86°

130 amps


Table 310.15 (b)(16) then ambient correction

34.) Hey 600 V 20 amp transformer will have an individual overcurrent device on the primary side rated at a largest of how many amps no overcurrent protection is utilized on the secondary side of the transformer

25 amps


Table 450.3