What are some types of control measures that shall be documented in the CSP? |
- Identity verification. |
|
SCIF perimeters include what? |
-all walls that outline the SCIF confines -floors -ceilings -doors -windows and penetrations by ductwork, pipes, and conduit. |
|
Closed storage areas that do not require discussion areas do not have any what?
|
forced entry or acoustic requirements.
|
|
Open storage facilities without SID require what? |
additional protection against forced and surreptitious entry
|
|
What type of wallboard is used in construction of SCIF walls?
|
5/8" Gypsum wallboard
|
|
What type of metal framing is used in SCIF walls? |
Three 5/8" wide, 16 gauge metal studs, mounted on a maximum of 16" o.c. |
|
What type of wooden framing or studs is used in SCIF walls?
|
2"x 4" studs mounted on a maximum of 16" o.c.
|
|
Continuous runners (same gauge as studs) for securing studs shall be anchored to what part of structures?
|
the true floor and true ceiling
|
|
In SCIF walls, the interior two layers of wallboard shall be mounted so that what do not align?
|
the seams
|
|
How shall acoustic fill shall be placed between the studs?
|
in a manner which prevents slippage
|
|
What type of wall is used for SCIFs designed for Closed Storage, Secure Working Area (SWA), Continuous Operation, or Open Storage with SID?
|
Wall A - Suggested Standard Acoustic Wall
|
|
SCIF wall penetrations shall be treated and sealed with what?
|
acoustic material
|
|
Entire wall assembly shall be finished and painted from _______ to ________?
|
true floor to true ceiling
|
|
What type of wall is used for SCIFs designed for Open Storage without SID? |
Wall B - Suggested Wall for Expanded Metal or Wall C - Suggested Wall for Plywood
|
|
Wall A SCIF walls use how many layers of wallboard?
|
Three
|
|
Expanded metal shall be spot-welded to the studs every ______ along the length of each vertical stud and ___________________?
|
every six inches, at the ceiling and floor
|
|
What may be used in lieu of welding to fasten metal to the studs?
|
hardened screws with one inch washers or hardened clips
|
|
What layer shall plywood walls have substitute for one layer of wallboard on the inside wall as compared to the standard acoustic wall?
|
one plywood layer
|
|
Where shall the plywood layer be continuously glued and screwed to the studs? |
every 12 inches along the length of each stud and at the ceiling and floor |
|
Installation of RF protection should be done using what guidelines? |
either the drawings or Best Practices Guidelines for Architectural Radio Frequency Shielding |
|
What are the three construction criteria for vaults?
|
- Federal Specification AA-V-2737 |