State minimum and maximum dimensions that a FDC can be from finished grade

Not less than 18" but not more than 4'

Minimum pipe size to serve a sprinkler system

Minimum 4 inch for fire engine connections


Minimum 6 inch for boat connections


Hydrauically calculated, permitted to be less than 4 inches but not less than the largest riser being served

Identify two pieces of equipment required on the FDC piping

Check valve and automatic drain/ball drip

Additional piece of equipment needed on the riser of a preaction system when installing the FDC

Check valve in the riser

State the purpose of a FDC for sprinkler systems

To pump supplement water into the sprinkler system, furnishing water to supplement existing water supplies

Position that most ball drips must be installed

Horizontally

State the situations when FDC can be omitted

Buildings located that are inaccessible for fire department support


Large capacity deluge systems exceeding the pumping capacity of the fire dept


Single story buildings not exceeding 2000 sq ft in area

Distance the FDC must be from the closest hydrant

NFPA - no requirements


OBC - 45 meters


Standpipe - 100 feet