60 Cards in this Set

  • Front
  • Back

What are the three sides of the fire triangle?

Oxygen, Fuel, Ignition Source

Heat is produced when materials react how to form simpler compound?

Exothermically

This is the most appropriate type of detection for a computer room

Air-Sampling smoke detection

A condition where a burning fuel produces smoke without flames is known as what?

Pyrolosis

What kind of detector is most appropriate for an elevator lobby in an apartment building

Spot-type smoke detector

During UL tests, system-powered smoke detectors must respond to a polystyrene fire within how much time?

2 minutes

The horizontal spacing for a detector in a room with five minutes per air change is how many feet?

25'

Rooms or spaces with high ceilings may be subject to what condition during a fire

Stratification

What kind of detector is most appropriate for an unenclosed, unheated parking garage?

Heat detector

Concealed duct smoke detectors mounted more than 10' above the floor must be provided with what?

Remote indicator

Temperatures lower than 32℉ and higher than 100℉ are not suitable for these types of detectors?

Smoke detectors

Due to humidity and chlorine corrosion, smoke detectors are not suitable for rooms containing what?

Swimming pools

These detectors must cause a supervisory signal where the signal in annunciated at a constantly attended location

Duct smoke detectors

What kind of detector is most appropriate for an atrium?

Projected-beam smoke detector

When these are used for for releasing service, they must be installed on both sides of the protected door

System smoke detectors

Stair pressurization is an example of what?

Smoke control function

Duct smoke detectors are required when the minimum air flow exceeds what?

2000 cfm

Air-sampling smoke detector sampling pipes must be labeled every how many feet?

20'

Fan shutdown, smoke exhaust and stair pressurization are all examples of what?

Smoke mitigation prevention

Cigar smoke, diesel exhaust, and humidity in excess of 93% can cause what in smoke detectors?

Nuisance alarms

A type-A public emergency reporting system recorded more than how many alarms per year?

2500

Before testing a protected premises system connected to a master box, what must be accomplished?

Plug out the box.

A public emergency alarm reporting system operates on what?

100mA DC loop

Central station service contract have what six elements?

-Installation of the transmitters


-Alarm, guards tour, supervisory and trouble signal monitoring


-Re-transmission


-Associated record keeping


-Testing and maintenance


-Runner service

For a central service station, the prime contractor is in compliance if the system is what?

Placarded and Certificated

Central station operators must RE-transmit an alarm signal to the public fire dispatcher how quickly?

Within 90 second

What type of signal do public emergency alarm reporting systems provide?

Alarm

Proprietary supervising stations must retain records for not less than how long?

12 months

Runners must communicate with the supervising station at intervals not exceeding how long?

15 minutes

A chain of hardware stores under one ownership, a college campus under one ownership, and a military base are all examples of properties that are permitted to be monitored by what?

Proprietary supervising station

Single station smoke alarms for dwelling use became available in what decade?

1970's

The primary purpose of dwelling fire warning equipment is what?

Life safety

Areas of a dwelling more than how many square feet require additional smoke alarms or detectors?

1000 ft

The actuation of these is not allowed to cause the actuation of the following: a) alarms in other dwellings, b) other alarms within the same building, c) the building fire alarm system

Multiple-station smoke alarms

This is the most appropriate type of detection in dwelling garages, unfinished attics or crawl spaces?

Heat detection

Wall mounted heart detectors must be mounted so the top of the detector is between 4in and how many inches from the ceiling?

12in

Heat detectors mounted on the ceiling must be at least how many inches from the wall?

4in

What is the maximum number of unmonitored smoke alarms that can be interconnected?

12

The NEC requires smoke alarms within how many feet of a range or cooktop to be either of the photoelectric type or to have a silence feature?

21ft

Dwelling heat detectors must be selected to operate at a temperature not less than how many degrees above the maximum expected ambient temperature in these protected space?

25℉

Household fire alarm system must be provided with how many sources of power?

2

Household fire alarm systems must have a secondary power source capable of providing not less than 24 hours of standby power followed by how many minutes of alarm?

4 minutes

A DACT on a dwelling fire alarm system must send a test signal to the supervising station how often?

Monthly

For alarm system controls in a one family home must conform to UL what?

UL 985

Verification calls to a dwelling may be placed prior to re-transmitting the alarm, provided the delay caused by the call does not exceed how long?

90 seconds

Who is responsible for ensuring fire alarm systems are properly tested?

The owner

This must be provided to the owner or the owners representative upon completion of testing a fire alarm system?

Site-specific software

The owner must retain the record of inspection and test for how long?

The life of the system

The audibility of horns are tested using what?

Sound pressure level meter

How often do non-restorable, fixed temperature heat detectors need to be tested?

Every 15 years

NFPA 72 requires service personnel to be qualified and what?

Experienced

Control functions of control equipment not monitored by a supervising station must be tested how often?

Annually

This test is conducted upon completion of the initial installation of a fire alarm system?

Acceptance test

This test is required after any change is made to the fire alarm system?

RE-acceptance test

This test is conducted periodically to ensure system operability and reliability?

Periodic

Aerosol smoke, incense sticks, punk sticks, and so on are used on smoke detectors in this type of test

Functional test

Technicians who are factory trained for certain products are only qualified to work on what?

Those certain products

A single open circuit on this type of fire alarm circuit will cause a trouble alarm but will not affect the operation of appliances?

Class A fire alarm circuit

The minimum sound pressure level (SPL) required for a sleeping room which has an average SPL of 50dBA is what?

75 dBA

Heat detectors installed on a packed ceiling of a dwelling must be installed so they are how far from the peak?

3'