Backflow is defined as

Unwanted flow of non potable water, used water, gas, industrial fluids etc into a potable water system.

Back siphonage is_____

A reversal of the normal direction in flow in a water supply line due to a negative pressure or vacuum being created in the system.

List 10 Back siphonage preventers

Air gaps


Atmospheric Vacuum breakers


Pressure vacuum breakers


Dual check Backflow preventers


Dual check Backflow preventers with atmospheric port


Dual check Backflow preventers with vent


Double check valve assembly


Hose connection vacuum breakers


Reduced pressure principal Backflow preventer


Laboratory faucet type vacuum breakers

Define back pressure

A reversal in flow where Water flows from a higher point in the system to a lower one,


A reversal in flow when the normal supply pressure is reduced or lost when there is high velocity flow in the main.

Back pressure/Backflow preventers rated by 3 degrees of hazard. What are they?

Minor, moderate, severe

How is an ‘ Air Gap’ rated ?

Severe in critical areas or where water is not required under pressure.

What is an RP?

Reduced pressure principle Backflow prevention Device

Certified testers successfully perform tests on what 3 devices?

Pressure Vacuum Breaker Assembly (PVB)


Double Check Valve Assembly (DCVA)


Reduced Pressure Principal Backflow prevention assembly ( RP)

Testers must be recertified every ____years or demonstrate-testing every _____ years.

5


2

Who is responsible for test certification requirements?

American Water Works Association


AWWA

Size of an air break:

1” or 1 pipe diameter

Air Gap

1” or 2 pipe diameter

Define Anti Siphon Breaker

Device installed on a line that is designed to prevent a Vacuum from forming in a piping system.


Installed max 1” from the top

Define an Atmospheric Vacuum Breaker (AKA non pressure type vacuum breaker)

A device containing a shut off valve followed by a valve body containing a disc float assembly a check seat and an air inlet port.

Location and max pressure of an atmospheric Vacuum Breaker

6” above flood level rim


12 hours

Atmospheric pressure

14.7 psia


101 KPA


29.92 inches of mercury

Define Back pressure Backflow preventer

Prevents Backflow due to condition in which pressure in the system become greater than the supply pressure.

Define Backflow preventer , double check valve type (DCVA)

Device consisting of 2 internally force loaded approved check valves installed between two shut off valves .

Describe an RP

Two independently acting force loaded check valves separated by an independently operating hydraulic differential pressure relief valve.

Define barometric Loop

A piping loop rising at least 35 feet at its uppermost point above the highest fixture it supplies. This is done to prevent Backflow and back pressure.

What is a check valve?

Self closing valve designed to permit flow in one direction, that closes if there is a reversal of flow.

In regards to a back siphonage preventer, what is the Critical Level (CL)?

Lowest level to which a back siphonage preventer can be submerged in water before Backflow begins.

Cross connection

Any unprotected ACTUAL or POTENTIAL piping connection or structural arrangement between public potable water system and any other source where it is possible to introduce used water, industrial fluids, gases or substances into the potable water system.

Describe a MINOR degree of Hazard:

Cross connection that would constitute a nuisance without any health hazards.

Describe a MODERATE hazard:

Cross connection that has low probability of becoming a severe hazard

Describe a SEVERE Hazard:

Cross connection or potential cross connection involving a substance that could be a danger to health.

Negative pressure is pressure ________atmospheric pressure, creating a ________

Below


Vacuum

What is a Vacuum Breaker?

Device designed to prevent back siphonage by providing an opening through which air may be drawn automatically to relieve negative pressure in the supply pipe

Define potable water

For for human consumption, free of impurities at harmful levels

Define non potable water

Unsafe for drinking or cooking

Possible cross connection

Where modifications to the piping system could result in a cross connection.

What is Backflow ?

Unwanted flow of non potable water into the potable system

What is the cause of back pressure?

Interconnection with another system operated at a higher pressure.

Backflow prevention devices must be ________, _______, _______ and ________ by the owner.

Inspected, tested, installed and maintained

List the areas where Air Gap is mandatory

- sewage handling plants


-non potable water systems


- presence of any Lethal substances

What is contamination?

Impairment of quality of water that creates an actual hazard to public health through poisoning or spreading of disease.

What is pollution?

Impairment of quality of water that does NOT create an actual Health Hazard.

List the diseases that can be carried in water and spread through cross connection

Amoebiasis


Cholera


Infection Hepatitis


Salmonellosis


Shigellosis


Paratyphoid


Typhoid Fever


What is the maximum height of a permanently installed device?

5’ or 1.5m above the floor or any platform

What class of contamination would medical gas fall into?

Severe

What method offers the best protection from cross connection?

Air Gap

What is the minimum protection to be used on a residential lawn sprinkler that uses no chemicals?

DCVA

A wet standpipe system with glycol would require what protection?

RP

What is the height requirement for clearance above the device for testing purposes?

1 foot

What is the minimum spacing below the device for testing purposes?

1 foot

Who has the jurisdiction of overall responsibility for health?

Health departments

List the responsibilities of the water purveyors:

Provide safe and potable water

List the responsibilities of the owner :

Prevent pollutants and contaminants from entering the public water system

At whos expense, shall the owners have tested and maintained , as directed by the authorities with jurisdiction .

They’re own

Certified cross connection specialist is responsible for :

Completely testing Backflow assemblies

The manufacturers of cross connection control devices must_____________________

Ensure all its devices conform to applicable standards and bear the necessary stamp of approval of an accredited agency like CSA

An open cat or water supply including a float operated inlet shall be protected by an_____

Air Gap back siphonage preventer

The minimum air Gap of a water supply pipe is ______the diameter of the effective opening of the ________

Two times


Outlet

Minimum air Gap shall be no less than ______”

1”

The Backflow prevention device that is open to the atmosphere shall not be located where _____________________

It could contaminate the water supply, and the opening cannot be submerged and spillage where it is open to the atmosphere would be undesirable

Reduced back pressure Backflow preventers are installed in the potable water supply service pipe to what types of facilities?

Medical treatment hospitals, fertilizer plants , meat packing plants , abattoirs, chemical plants

An atmospheric Vacuum Breaker shall be used on supplies that are ______and ____

Non Toxic


Non Lethal

An atmospheric Vacuum Breaker shall never be installed lower than _____” above the flood level rim

12”

The pressure vacuum shall never be used where it is subject to _______, and the device has a valve _______ of it.

Back pressure


Downstream

An atmospheric Vacuum Breaker must be installed so it’s critical level is not less than _____” when it is installed in other that a water closet tank and __” when it is used in a water closet tank.

6”


1”

The required distance for a pressure vacuum breaker above the flood level rim is ______”

12”

What hazard is the double check valve assembly used for?

Moderate

What hazard is an RP used for?

Severe

How many check valves does an RP device have?

2

How many check valves does a pressure vacuum breaker have?

1

Does

Lawn service

Define effective opening

Diameter of supply opening

Does an air Gap have mechanical parts?

No

What is the distance required above a double check valve assembly when using sight tubes for testing?

900mm/3’

The reduced pressure principal Backflow preventer is used for what type of protection only?

Back Siphonage and back pressure

The atmospheric Vacuum Breaker is used for protection from contamination by _______

Back siphonage

At atmospheric Vacuum Breaker must be installed ______ above the highest outlet of the flood level rim of all fixtures

6”

The atmospheric Vacuum Breaker shall not be installed where it is under continuous flow for more than ______hours

12