In what three ways does the human body lose heat?
|
evaporation ,
convection radiation |
|
Comfort is ________?
|
comfort is when the human body feels neither warm nor cool
|
|
Snow melting is an added feature to a hydronic system T/F
|
True
|
|
comfort is achieved by heating the body T/F
|
false, comfort is achieved by controlling the rate and manner in which heat is lost from the body
|
|
Radiant heat is not comfortable heat.T/F
|
False, radiant heat is a comfortable heat... convection heat is not comfortable.
|
|
Hydronic heating systems CAN provide different temperatures in various portions of a home.T/F
|
True
|
|
A Hydronic heating system CAN be used to heat domestic water T/F
|
True
|
|
A snow melting system CAN be provided by a hydronic system T/F
|
True
|
|
Excess moisture in a home is harmful to building construction T/F
|
True
|
|
The size of a compression tank in a hydronic system is NOT critical T/F
|
False, inadequate room for expansion defeats economy.
|
|
In what three ways does the human body lose heat?
|
evaporation ,
convection radiation |
|
Comfort is ________?
|
comfort is when the human body feels neither warm nor cool
|
|
Snow melting is an added feature to a hydronic system T/F
|
True
|
|
comfort is achieved by heating the body T/F
|
false, comfort is achieved by controlling the rate and manner in which heat is lost from the body
|
|
Radiant heat is not comfortable heat.T/F
|
False, radiant heat is a comfortable heat... convection heat is not comfortable.
|
|
In what three ways does the human body lose heat?
|
evaporation ,
convection radiation |
|
Comfort is ________?
|
comfort is when the human body feels neither warm nor cool
|
|
Snow melting is an added feature to a hydronic system T/F
|
True
|
|
comfort is achieved by heating the body T/F
|
false, comfort is achieved by controlling the rate and manner in which heat is lost from the body
|
|
Radiant heat is not comfortable heat.T/F
|
False, radiant heat is a comfortable heat... convection heat is not comfortable.
|
|
Hydronic heating systems CAN provide different temperatures in various portions of a home.T/F
|
True
|
|
A Hydronic heating system can be used to heat domestic water.T/F
|
True
|
|
A snow melting system can be provided by a hydronic system T/F
|
True
|
|
Excess moisture in a home is harmful to building construction T/F
|
True
|
|
The size of a compression tank is not critical.T/F
|
False, Inadequate room for expansion defeats economy.
|
|
A compression tank is not necessary in a system if a pressure reducing valve is used T/F
|
False, compression tank and PRV serve separate functions and must both be used.
|
|
You should NOT plug a relief valve if it continues to drip T/F
|
True , it should be replaced
|
|
All closed hot water heating systems should have both a Pressure reducing valve and a relief valve.T/F
|
True
|
|
Relief Valves installed on residential hydronic systems are factory set to relieve water or steam if the systems pressure exceeds 30 psig T/F
|
True
|
|
It IS necessary to install flow-control valves if a hot water heating boiler is equipped with a heater for domestic water T/F
|
True
|
|
The difference in weight of water in the supply and return mains will create circulation in a gravity hot water heating system T/F
|
True
|
|
The heat emission rate of gravity system is 150-165 BTUH per square foot of radiation T/F
|
True
|
|
Two advantages of using higher temperature heating system are a smaller size radiation unit and a smaller size pipe.T/F
|
True
|
|
A closed hydronic heating system allows you to have higher water temperatures than in open gravity systems.T/F
|
True
|
|
Water temperatures in a closed hydronic heating system DO NOT affect the sizes of radiation piping. T/F .
|
False,
|
|
A compression tank is not necessary in a system if a pressure reducing valve is used T/F
|
False, compression tank and PRV serve separate functions and must both be used.
|
|
You should NOT plug a relief valve if it continues to drip T/F
|
True , it should be replaced
|
|
All closed hot water heating systems should have both a Pressure reducing valve and a relief valve.T/F
|
True
|
|
Relief Valves installed on residential hydronic systems are factory set to relieve water or steam if the systems pressure exceeds 30 psig T/F
|
True
|
|
It IS necessary to install flow-control valves if a hot water heating boiler is equipped with a heater for domestic water T/F
|
True
|
|
The difference in weight of water in the supply and return mains will create circulation in a gravity hot water heating system T/F
|
True
|
|
The heat emission rate of gravity system is 150-165 BTUH per square foot of radiation T/F
|
True
|
|
Two advantages of using higher temperature heating system are a smaller size radiation unit and a smaller size pipe.T/F
|
True
|
|
A closed hydronic heating system allows you to have higher water temperatures than in open gravity systems.T/F
|
True
|
|
Water temperatures in a closed hydronic heating system DO NOT affect the sizes of radiation piping. T/F .
|
False,
|
|
A compression tank is not necessary in a system if a pressure reducing valve is used T/F
|
False, compression tank and PRV serve separate functions and must both be used.
|
|
You should NOT plug a relief valve if it continues to drip T/F
|
True , it should be replaced
|
|
All closed hot water heating systems should have both a Pressure reducing valve and a relief valve.T/F
|
True
|
|
Relief Valves installed on residential hydronic systems are factory set to relieve water or steam if the systems pressure exceeds 30 psig T/F
|
True
|
|
It IS necessary to install flow-control valves if a hot water heating boiler is equipped with a heater for domestic water T/F
|
True
|
|
The difference in weight of water in the supply and return mains will create circulation in a gravity hot water heating system T/F
|
True
|
|
The heat emission rate of gravity system is 150-165 BTUH per square foot of radiation T/F
|
True
|
|
Two advantages of using higher temperature heating system are a smaller size radiation unit and a smaller size pipe.T/F
|
True
|
|
A closed hydronic heating system allows you to have higher water temperatures than in open gravity systems.T/F
|
True
|
|
Water temperatures in a closed hydronic heating system DO NOT affect the sizes of radiation piping. T/F .
|
False,
|
|
A compression tank is not necessary in a system if a pressure reducing valve is used T/F
|
False, compression tank and PRV serve separate functions and must both be used.
|
|
You should NOT plug a relief valve if it continues to drip T/F
|
True , it should be replaced
|
|
All closed hot water heating systems should have both a Pressure reducing valve and a relief valve.T/F
|
True
|
|
Relief Valves installed on residential hydronic systems are factory set to relieve water or steam if the systems pressure exceeds 30 psig T/F
|
True
|
|
It IS necessary to install flow-control valves if a hot water heating boiler is equipped with a heater for domestic water T/F
|
True
|
|
The difference in weight of water in the supply and return mains will create circulation in a gravity hot water heating system T/F
|
True
|
|
The heat emission rate of gravity system is 150-165 BTUH per square foot of radiation T/F
|
True
|
|
Two advantages of using higher temperature heating system are a smaller size radiation unit and a smaller size pipe.T/F
|
True
|
|
A closed hydronic heating system allows you to have higher water temperatures than in open gravity systems.T/F
|
True
|
|
Water temperatures in a closed hydronic heating system DO NOT affect the sizes of radiation piping. T/F .
|
False,
|
|
The BTU output of a boiler can be increased by raising the boiler water temperature.T/F
|
True
|
|
Resistance (Pressure Drop) affects the length of a series loop circut.T/F
|
True
|
|
A circuit in a one-pipe system decreases in size as radiation is taken off of it .T/F
|
False,
|
|
Piping connections to risers or room units are usually taken out of the top of the mains at either a 45 or 90 degree from the horizontal main .T/F
|
True
|
|
A two-pipe reverse return system should be provided with diversion tees at the room unit take-offs T/F
|
False,
|
|
The supply circuit of a two-pipe reverse return circuit diminishes in size as room units are returned into the circuit.T/F
|
True
|
|
The return circuit of a two-pipe reverse circuit diminishes in size as room units are returned into the circuit T/F
|
False,
|
|
The BTUH carrying capacity of a pipe decreases as the velocity of water in that pipe increasesT/F
|
False,
|
|
It is not necessary to calculate the pressure drop of a system to size the piping and the circulating pump.T/F
|
False,
|
|
Static pressure is greatest at lowest parts of the hydronic system T/F
|
True
|
|
Static pressure has no effect on pump operation in a closed system .T/F
|
true
|
|
A milinch is a measure of temperature.T/F
|
False, A milinch is a measure of volume.
|
|
It is permissible to install baseboard radiation on an inside wall if necessary .T/F
|
True
|
|
Room heating units,such as baseboards,convectors,radiators,etc..are sized to the heat loss of the room.T/F
|
True
|
|
Average water temperature does NOT enter into the sizing of room units T/F
|
False
|
|
Radiation units should be placed under windows and on outside walls as much as possible
|
True
|
|
Cast iron baseboard is NOT recommended for residential use T/F
|
False
|
|
Most residential copper fin tube baseboard heating elements consist of 3/4" seamless copper tube with attached fins.T/F
|
True
|
|
The height of a convector enclosure affects the BTUH output.T/F
|
True
|
|
Pressure drop through a convector does NOT affect the size of it's piping connections.
|
False
|
|
As the water temperature from a boiler becomes greater, the heating output of the radiation becomes greater.t/f
|
True
|
|
Heating elements for convector type baseboards are furnished in 6' lengths or less T/F
|
True
|
|
Cast iron radiant baseboards function similar to a radiant convector T/F
|
True
|
|
Piping for hot water heating returns CANNOT be installed in the same convector type baseboard enclosure along with a finned tube heating element.T/F
|
False
|
|
In what three ways does the human body lose it's heat?
|
radiation
convection evaporation |
|
What are four advantages of heating domestic hot water with a hot water heating boiler?
|
1-ample hot water
2-continued boiler use, prevents deterioration 3- Boiler heat loss helps keep the basement dry 4- Ready instatnly during sudden temperature loss |
|
List Two of the options available for summer cooling in conjunction with hydronic heating:
|
1- use baseboard hydronic units for heating
2-combination heating and cooling units |
|
What are two advantages of using a higher temperature heating system ?
|
1-smaller pipe
2- smaller sized radiator unit |
|
List three types of hydronic heating systems
|
1-series loop
2- one pipe 3- two pipe |
|
What is a milinch?
|
1/1000 of an inch
|
|
What is static pressure?
|
weight of water in the system and is equal the .433 psi per foot of height above the guage.
|
|
What are three ways pressure drop is expressed?
|
1- Psi
2- milinch 3-feet of water |
|
What creates circulation in a forced hot water heating system?
|
circulating pump
|
|
What is pressure drop?
|
Pressure drop is the amount of pressure lost between any two points in a system.
|
|
What causes pressure drop?
|
Power or energy consumed by moving through piping heating or cooling units, fittings etc friction in short.
|