Which traps need not be vented?

Subsoil drainage or storm drainage.


The absence of sewer gases.

Maximum number of water closets vented through a wet vent?

Two

How must 2 water closets be installed to both be wet vented if the vent pipe is vertical?

At the same level by means of a double sanitary T

What is a wet vent in simple terms?

A section of pipe that serves as both a drain and a vent.

How must 2 water closets be wet vented if the vent pipe is horizontal?

Double Y fitting

Wet vented water closets must be installed _________ of all other fixtures .

Downstream

Trap arms and fixture drains connecting to the wet vent do not exceed 2 inches in size except for?

Connections from emergency floor drains.

What table determines hydraulic load permitted for a wet vent?

2.5.8.1.

Separately vented fixtures are _____________when sizing the continuous vent that serves the wet vent.

Not included

When a Wet vent vent extends through more than 1 story the total discharge from any 1 story above the first story does not exceed ___ fixture units.

4

What is the limit on the length of a wet vent?

There is no limit

Wet vented portion of pipe is not reduced in size ( continuous throughout) except ________

For the portion upstream of an emergency floor drain.

A section of a HORIZONTAL BRANCH is permitted to be circuit vented provided that:


A)


B)


C)

A) a circuit vent is connected to it.


B) all fixtures served by the circuit vent are in the same story


C)no soul or waste is connected upstream of a circuit vented fixture.

Fixtures with fixture outlets pipes less than 2 inches shall be ______

Separately vented or separately circuit vented.

A relief vent shall be connected to the branch that forms part of the circuit vented system , downstream of the connection of the ________

most down stream circuit vented fixture .

What is the maximum hydraulic load of a soil or waste pipe permitted to act as a relief vent?

6 fixture units

A symmetrically connected relief vent is permitted to serve as a combined relief vent for a maximum of 2 branches that are circuit vented , provided there are _______

Not more than 8 circuit vented fixtures connected between the combined relief vent and each circuit vent.

Where are additional circuit vents required? ( 2 items)

1) where each cumulative horizontal change in direction of a branch serves by a water closet exceeds 45• between vent pipe connections


2)where more than 8 circuit vented fixtures are connected to a branch between the circuit and relief vents.

A soil or waste pipe is permitted to serve as an additional circuit vent provided that:

The soil or waste pipe is 2” or larger and sized as a wet vent in accordance to 2.5.8.1.

Hydraulic load of a circuit vent from fixtures connected to the branch served by a circuit vent but shall not include the hydraulic load from _______

The first or most upstream fixture

What shall the upper end of every soil and waste stack terminate in?

Stack vent

When must we install a vent stack?

(1)When the soil or waste stack exceeds 4 stories unless (2) the soil or waste stack serves as a wet vent.

Where must a vent stack connect to a soil and waste stack?

In the vertical sections at or immediately below the lowest soil or waste connection to the soil and waste stack.

Fixtures are permitted to be connected to a vent stack provided :

A)total hydraulic load of connected fixtures does not exceed 8 fixture units.


B)at least one fixture is connected to a vertical portion and upstream of any other fixture.


C) no other fixture is located downstream of a water closet.


D)all fixtures are located on the lowest story served by the vent stack


E) the sections of the vent pipe that acts as a wet pipe confirms to that.

What is a yoke vent?

A connection between the vent stack and soil and waste stack to provide extra circulation.

When is a Yoke vent required?

When a soil and waste stack receives discharge from 11 or more stories.

How often must a yoke vent connection be installed?

Every 5 stories from the top down and wherever there is an offset or double offset.

Yoke vent shall be connected with a ________ at or _____________.

Drainage fitting


At or immediately below the the lowest soil or waste pipe connected to the soil or waste stack.

Yoke vent must be installed at least ______ above the floor level of the lowest story in the 5 story section .

1m

A Yoke vent is not needed when

The waste stack and vent stack are interconnected on each and every floor by a vent pipe.

When do we need an offset relief vent?

When the nominally horizontal offset is more than 1.5 m and the upper vertical portion passes through more than 2 stories and receives a hydraulic load of more than 100 fixture units.

When may a trap arm (that has a hydraulic load of no more than 1 1/2 fixture units) of a fixture drain into a the vertical section of a ( circuit, relief, additional or Yoke) vent?

Where not more than 2 fixtures are connected to the vent pipe , when 2 fixtures are connected by a double sanitary T, the section that acts as a wet vent is not less than 2 inches.

All sump pumps that receive sewage shall be ______

Provided with a vent pipe at the top of the sump

Every oil interceptor shall be processed with 2 vent pipes that connect to the interceptor at ____________, extend ________ to outside air, terminate not less than ________ above ground and at elevations differing by at least _______

opposite ends.


independently


2m


300mm

How must adjacent compartments of an oil interceptor be connected?

By a vent opening

Secondary oil receivers shall be vented in accordance of manufacturers specs and shall be in no case less than ______in size, extend _______ to outside air and terminate not less than _____ above ground.

11/2” in size ,


independently


2m

Vent pipes that serve oil interceptors shall be not less than 3” in size in areas where_____

It may be subject to frost closure.

fresh air inlet on a building trap must be installed not less than ___ in size , and connected ________ and within ____of said trap and downstream of ___________

4”


Vertically


1.2m


any other connection.

What size must a vent pipe be installed for a provision of future connections?

1 1/2”

Why must vent pipes be installed free of depressions?

To avoid areas where moisture can collect.

Except for wet vents, where shall vent pipes be connected to horizontal soil and waste pipes ?

Above the center line .

What shall be installed to unused vent pipes for futures?

Permanently capped with end clean out or adapter and plug .

Developed length of a trap shall not be less than _______ of the fixture drain.

Twice the size

Total fall of a trap arm must not be :

Greater than its inside diameter and does not have a cumulative change in direction of 135•

Max change in direction of trap arms for water closets?

225•

For water closets, what is the maximum distance of the fixture drain between the fixture and the vent pipe ?

1m vertical and 3 m horizontally

Water closet depend on what for proper function?

Siphonic action

Except for a wet vent , every vent pipe shall extend above the flood level rim of every fixture before_____

Being connected to another vent pipe

Where must all vent pipes terminate in a building 4 storeys or less ?

Through the roof.

How far from an air inlet, window or door must a vent terminate to outside air ?

Not less than 1m above and not less 3.5 in any direction from

How must a vent terminal be installed in a roof that supports and occupancy (deck, pool)?

At least 2m above and 3.5 in any direction away from .

How far above ground and from a property line must a vents terminate ( 2 answers)

Min 2m


Min 1.8m

Min distance above storm water ponding on a roof a vent shall terminate ?

150mm

What must be installed to prevent water from entering the building between vent and roof?

500mm X 500mm of flashing

How do we prevent front closure in a vent pipe ?

Increasing diameter by one size ( not less than 3”) before penetrating roof or


Insulating pipe

What is table 2.5.7.1.?

Minimum permitted pipe size of vent based on size of trap served.

Hydraulic Load of bathtub (w/or w/out shower)

1 1/2

Hydraulic load of a floor drain?

2

Size of Vent pipe based on 1 1/4” and 1 1/2” traps?

1 1/4”

Size of a vent pipe based on a 2,3 or 4” trap?

1 1/2”

Minimum size of vent pipe for 5” and 6” traps?

2”

Fixture units for a Lavatory?

1” w/ 11/4” trap


11/2 for a common 11/2 trap serving a 2 lavs

Fixture units for showers


A) 1 head


B)2-3 heads


C) 4-6 heads

A) 11/2fu


B) 3FU


C) 6FU

Minimum size of a vent pipe for a manhole?

2”

Minimum size of vents for a building drain ?

3”

Min and max size of additional circuit vents and relief vents ?

One size smaller than vent pipe and not more than 2”

Minimum size of offset relief vent?

One size smaller than size of stack vent

Minimum size of a Yoke vent

One size smaller than size of smallest pipe to which they are connected.

Minimum and maximum size of a vent for a sewage sump

One size smaller to a min of 2” and a max of 4”

Min size for a macerating toilet ?

11/2”

Basis of Table 2.5.7.1.

Minimum permitted size of vent pipe based on trap served.

Basis of Table 2.5.8.1.

Maximum permitted Hydraulic loads drained to a wet vent

When sizing an __________vent it a _____vent the length is not taken into consideration.

Individual


Dual

What table is used to size individual and dual vents? What is it based on?

2.5.7.1.


Size of largest trap served

What table is used to size Branch vents, vent headers, circuit vents and continuous vents?

2.5.8.3.

The Length of a VENT HEADER shall be it’s developed length___________

From the most distant soil or waste pipe connection to outside air.

The length of a CIRCUIT VENT shall be it’s developed length from ________________ connection to a __________,__________,________ or outside air.

horizontal soil and waste connection


vent stack , stack vent, vent header

What table do you use to size branch vents , vent headers, circuit vents and continuous vents?

2.5.8.3.

What information is needed to size a Stack Vent or vent stack on table 2.5.8.4.?

Table 2.5.8.4.


You need the size of the soil and waste stack at its base, total hydraulic load being vented and the developed length.

for which vents is length not taken into consideration when sizing vents?


There’s 8 of them. ****

Additional circuit vents, offset relief vents, relief, Yoke and vents pipe for interceptor, dilution tanks, sewage tanks and manholes

What 4 places can air admittance valves be used?

1) island sinks/fixtures


2)fixtures affected by frost closures


3)1 and 2 family dwellings under renovations where vent connections may not be practical


4) installations where it may not be practical

Air admittance valves shall be installed according to what?

Manufacturers instructions.

Size a Dual Vent

Size of largest trap


2.5.7.1.

Size an individual vent

Size of largest trap


2.5.7.1.

Hydraulic Load of a Stall type Urinal

2

Size a continuous vent

Hydraulic load of wet vented fixtures served and developed length


2.5.8.4.


2.5.7.1.

Size a Stack Vent

Hydraulic load at base of stack served, hydraulic load of additional vents connected , length of stack vent

2.5.8.4.


2.5.7.1.

Size Vent headers

Hydraulic load at base of stacks, hydraulic load of additional vents connected , length of header , min 1/2 size of stack at its base.

2.5.8.3


2.5.7.1.

Sizing criteria for Wet Vent

Hydraulic load draining into lowest portion of wet vent , no more than 2 WC symmetrically connected , wet vent full size throughout, no more than 4 FU/storey above first story, except most downstream.

2.5.7.1.


2.5.8.1.

Hydraulic load of a wall type washout urinal?

11/2

Hydraulic load of a Water closet?

4

Sizing circuit vents

Hydraulic load draining into section being sized requires a relief vent downstream of lowest fixture outlet less than 2” must be individually vented or separately circuit vented.

A continuous vent is considered to be a _______vent.

Dry

Yoke vents must be installed in buildings that receive discharge from fixtures located in more than ____ stories

11

The developed length of a continuous vent is measured from the __________ soil and waste pipe connection to a _______, _________, _______ or open air . This is found in clause#_____

Vertical


Vent stack, stack vent, vent header


2.5.8.3.

List the conditions in which a nominally horizontal offset will require 2 offset relief vents.

Offset is greater than 1.5m


Upper vertical portion of the stack passes through more than 2 stories


Received a hydraulic load of more than 100 fixture units.

Size a relief vent

One size smaller than circuit vent


2.5.7.1.

Size additional circuit vent

One size smaller than circuit vent-max 2”


2571

Size Offset relief vents

2 required


One size smaller than stack vent

Size Yoke vent

One size smaller than pipe connected to

Minimum size for a Manhole Vent ?

2”

Sump Vent

One size smaller than largest inlet


Min 2”, max 4”

Oil interceptor Vents

2 required , min 11/4”

Fresh Air inlets

Min 4” less than 1.2m upstream ( for building traps)

What is an island vent?

Vent used to vent a fixture installed in a location where it is impossible to connect the vent above the flood level rim of the fixture being vented.

When connecting a fixture using an island vent , what must the drainage and piping also be equipped with under a floor?

Clean out

When connecting a fixture using an island vent which code/tables must be used to size the drain and vent?

2493


2571

What must be done to the lowest point of the vent piping when using an island vent?

Drained to the fixture drain

When is it permissible to install an island vent?

When there is no direct access to an adjacent wall

What is the purpose of a vent stack?

Limits the pressure differentials in a soil and waste stack

How high must a building be before a vent stack is required?

More than 4 stories with plumbing fixtures

Where must a vent stack connect?

At or below the lowest soil or waste branch connected to the stack

What story must a vent stack connect to the soil and waste stack?

The lowest story served by the stack

Where is a bathroom group allowed to be drained into a vent stack?

Lowest story served by the vent stack.

When a bathroom group is connected to a vent stack, is it necessary to connect a fixture to the vertical portion of the vent stack?

Yes, at least one fixture must be connected to the vertical portion.

How many fixture units are allowed to connect to the vent stack?

Eight fixture units

How is a bathroom group sized when tied in to the vent stack?

As a wet vent

What is the purpose of a Yoke vent?

Relieves excessive air pressures

When an offset in a soil or waste stack is greater than 1.5m, how is it sized?

As a branch or building drain


2.4.10.6.